The Backflow Testers of Chula VistaCall (619) 648-5392

Backflow Assembly Testing in Chula Vista

Here's how the test actually works.

We hook a calibrated gauge to the little test valves on the device, close the shutoffs and see if each check holds. On an RP we also check the relief valve. The numbers go on the district's form.

Easiest way? Just call.

  • Price$105 flat
  • TimeUnder an hour
  • SchedulingSame week
  • FilingIncluded

Pricing

Backflow sizeFlat fee per backflow
Under 4"$105
4" and larger$175

Includes the test and filing with your water district. No hidden fees.

On every test

  • Both shutoffs seal
  • Vacuum breaker air inlet works
  • No visible leaks or damage
  • Check valves hold above the minimum
  • RP relief valve opens on time

Calibrated equipment, accurate readings

Every backflow test depends on a differential pressure gauge. It measures the small pressure differences across each check valve and, on an RP, the point where the relief valve opens. Those numbers decide whether your device passes.

A gauge that reads even slightly off can pass a bad device or fail a good one. That's why water districts require test gauges to be checked for accuracy on a regular schedule, and why our gauges are kept in calibration.

It's also why a test has to be done by a certified tester. Certification means the tester has been trained on the procedures and passed an exam on them. Your district won't accept a report without a certified tester's signature and the gauge details listed.

Step by step through an assembly test

First, the tester makes sure the assembly is the right type for the connection and that nothing obvious is broken. Then the test cocks are flushed to clear out debris that could throw off the readings.

Next, the downstream shutoff valve is closed. With the gauge hooked to the test cocks, the tester measures how well the first check holds, then the second. On an RP, the relief valve opening point is measured too. On a vacuum breaker, the air inlet and check are tested instead.

Finally, the tester opens the valves, checks for leaks, and puts the test cock caps back on. The whole process for a typical assembly takes 20 to 45 minutes. Larger devices and ones in tight spaces can take a bit longer.

The usual causes of a failed test

The most common reason a test fails is debris. Sand, rust flakes and bits of pipe sealant travel down the water main and get caught on a check valve seat, keeping it from closing all the way. A cleaning often fixes it.

Worn rubber is next. Check discs and o-rings harden and crack with age, heat and chlorine in the water. Rebuild kits replace those parts for a fraction of the cost of a new device.

Less often, a spring has weakened, a relief valve diaphragm has torn, or the body is cracked from freezing or impact. Springs and diaphragms are repairable. A cracked body usually means replacement. Whatever the cause, we show you the reading and explain it before any work starts.

What goes on the test report

Your water district judges compliance by the report, not the visit. The report shows the address, the device make, model, size and serial number, its location, and every reading taken.

It also carries the tester's certification and gauge details, plus the result: pass, fail, or pass after repair, with any replaced parts listed.

Districts don't all use the same form, and many have deadlines for submitting reports after a test. We take care of that part and send you a copy. Keep it somewhere easy to find, since escrow companies, landlords and city inspectors sometimes ask for it.

Test cocks and shutoff valves

Every assembly has test cocks, the small fittings the gauge attaches to, and a shutoff valve at each end. Both have to work for the test to be valid.

The tester checks them first. A clogged test cock can usually be cleared right away. A shutoff that won't close all the way may need repair before an accurate test is possible, and we'll tell you if so.

Testing after repairs, moves and installs

Annual tests aren't the only ones. After any repair, the assembly must be retested. When a device is relocated or reinstalled, it's tested again. New devices get a startup test.

The procedure is the same each time, and each produces a report for the district. If we did the work, that follow-up test is part of the job.

What if it fails?

We show you which reading failed and quote the repair. More on assembly repair.

Questions

Can a device pass one year and fail the next?

Yes. Debris and wear build up over time, which is exactly why the test is yearly.

How long does an assembly test take?

Most take 20 to 45 minutes per device, depending on size and access.

Is the gauge calibrated?

Yes. Districts require test gauges to be calibrated on a schedule, and ours are.

Will I see the readings?

Yes. They're on your copy of the report, and the tester can walk you through them on site.

Do you need to shut my water off?

Only for a few minutes during the test. We'll let you know before we close the valves.

Who gets the test results?

Your water district gets the report, and you get a copy too.

Why folks in Chula Vista call us

Backflow is what we do. Our testers are certified, our gauges are calibrated, and we send the report to your water district for you, every time.

No surprises on price: $105 for devices under 4 inches, $175 for 4 inches and up, and free quotes on everything else. We answer seven days a week, 6am to midnight, and emergencies around the clock.

Here's how a visit goes. We call or text when we're on the way, find the device, and get the test done. If it passes, that's it: we file the report and send you a copy. If it doesn't, we'll show you what's wrong, tell you the price and fix it if you want us to. Most folks around Chula Vista never need to be home for any of it.

Chula Vista and nearby

We do backflow assembly testing in Chula Vista, National City, Paradise Hills, Bonita, Imperial Beach and Encanto. We can usually come out this week.

Let's get it done

Same-week visits around Chula Vista. We do the paperwork.

Call nowBook online